Kitchen Extraction Not Working? Common Faults and What to Do

Smoke spilling from the canopy, a dead fan or a tripping gas interlock? The common causes of commercial kitchen extraction faults and what to do first.

What should I do if my commercial kitchen extraction stops working?

Stop cooking on gas appliances if the extraction has failed or the gas interlock has cut in, never bypass the interlock, check the basics such as isolators, filters and the fan, and call a competent engineer. Common causes are a failed fan or belt, blocked filters, a tripped isolator or missing make-up air.

Last updated

Maintenance13 Nov 20267 min read
Kitchen Extraction Not Working? Common Faults and What to Do

Safety first

If the extraction has failed and gas appliances are in use, the gas interlock should cut the gas. Do not bypass it. Stop cooking, ventilate the kitchen if you can do so safely and call a competent engineer. Gas work must be carried out by a Gas Safe registered engineer.

Quick checks

  1. Is the extraction isolator or switch on, and has the breaker tripped?
  2. Are the baffle filters in place and clean?
  3. Is the fan running, and at normal speed?
  4. Is the make-up air supply running?
  5. Is the gas interlock showing a fault?

If you cannot find the cause in minutes, call for help rather than keep trying.

Common faults and causes

SymptomLikely causes
Fan not runningTripped breaker, failed motor or belt, control fault
Fan running but little airflowBlocked filters, greasy duct, closed damper, reversed rotation, no make-up air
Smoke spilling from the canopyUndersized canopy, low airflow, draughts, blocked filters, no make-up air
Gas interlock trippingReal low airflow, sensor fault, belt slipping
Noise or vibrationWorn bearings, loose or unbalanced impeller
Smell of burningGrease build-up, overheated motor, slipping belt

Why make-up air is often the cause

A fan can only remove as much air as can get in. HSE says the ventilation design should take account of the need to replace extracted air (CAIS10). If a kitchen has been sealed up, or the supply fan has failed, the extraction will underperform. See make-up air in commercial kitchens.

Repair, replace or redesign?

A one-off failure is usually a repair. Repeated failures, an old system or a change in cooking may point to replacement or redesign; see when to replace a commercial extraction system.

Keep a fault log

Record the date, symptom, what was checked and what fixed it. Patterns appear quickly: a fault that returns after every busy weekend points to blocked filters or airflow; one that follows a power cut points to controls. A log helps the engineer find the cause faster, shows whether repairs are becoming frequent enough to justify replacement and provides the records that inspectors and insurers like to see.

Getting help

For urgent or emergency problems, call or WhatsApp 07759 696007 rather than waiting for an email reply. We cover customers across the UK; see our maintenance and servicing page.

Sources and further reading

Independent references we used, so you can check the rules yourself:

Frequently asked questions

Can I keep cooking if the extraction fails?

Not on gas appliances relying on it. The interlock should cut the gas; do not bypass it. Stop and get it fixed.

Why does my gas interlock keep tripping?

Usually low airflow from blocked filters, a slipping belt, a failed fan or missing make-up air.

Can you repair extraction systems?

We survey, repair and maintain systems; call 07759 696007 to discuss the fault.

How can I avoid breakdowns?

Planned maintenance, regular filter cleaning and prompt action on warning signs.