Safety first
If the extraction has failed and gas appliances are in use, the gas interlock should cut the gas. Do not bypass it. Stop cooking, ventilate the kitchen if you can do so safely and call a competent engineer. Gas work must be carried out by a Gas Safe registered engineer.
Quick checks
- Is the extraction isolator or switch on, and has the breaker tripped?
- Are the baffle filters in place and clean?
- Is the fan running, and at normal speed?
- Is the make-up air supply running?
- Is the gas interlock showing a fault?
If you cannot find the cause in minutes, call for help rather than keep trying.
Common faults and causes
| Symptom | Likely causes |
|---|---|
| Fan not running | Tripped breaker, failed motor or belt, control fault |
| Fan running but little airflow | Blocked filters, greasy duct, closed damper, reversed rotation, no make-up air |
| Smoke spilling from the canopy | Undersized canopy, low airflow, draughts, blocked filters, no make-up air |
| Gas interlock tripping | Real low airflow, sensor fault, belt slipping |
| Noise or vibration | Worn bearings, loose or unbalanced impeller |
| Smell of burning | Grease build-up, overheated motor, slipping belt |
Why make-up air is often the cause
A fan can only remove as much air as can get in. HSE says the ventilation design should take account of the need to replace extracted air (CAIS10). If a kitchen has been sealed up, or the supply fan has failed, the extraction will underperform. See make-up air in commercial kitchens.
Repair, replace or redesign?
A one-off failure is usually a repair. Repeated failures, an old system or a change in cooking may point to replacement or redesign; see when to replace a commercial extraction system.
Keep a fault log
Record the date, symptom, what was checked and what fixed it. Patterns appear quickly: a fault that returns after every busy weekend points to blocked filters or airflow; one that follows a power cut points to controls. A log helps the engineer find the cause faster, shows whether repairs are becoming frequent enough to justify replacement and provides the records that inspectors and insurers like to see.
Getting help
For urgent or emergency problems, call or WhatsApp 07759 696007 rather than waiting for an email reply. We cover customers across the UK; see our maintenance and servicing page.
Sources and further reading
Independent references we used, so you can check the rules yourself:
- HSE: Ventilation in catering kitchens (Catering Information Sheet 10)
- HSE: Gas safety in catering and hospitality (CAIS23)
- Gas Safe Register
Frequently asked questions
Can I keep cooking if the extraction fails?
Not on gas appliances relying on it. The interlock should cut the gas; do not bypass it. Stop and get it fixed.
Why does my gas interlock keep tripping?
Usually low airflow from blocked filters, a slipping belt, a failed fan or missing make-up air.
Can you repair extraction systems?
We survey, repair and maintain systems; call 07759 696007 to discuss the fault.
How can I avoid breakdowns?
Planned maintenance, regular filter cleaning and prompt action on warning signs.